Wire & Watts

10 vs 12 gauge wire for a 20 amp circuit

Updated by Biel Vazquez

Short answer: 12 AWG copper is correct for a 20 A circuit and is all the code requires. Use 10 AWG when the run is long: past about 50–60 ft at heavy load, 12 AWG drops more than the 3% the NEC recommends, while 10 AWG keeps it under 3% to roughly 90 ft.

What the code says

NEC Table 310.16 gives 12 AWG copper an ampacity of 20 A in the 60 °C column, and NEC 240.4(D) caps 12 AWG copper at a 20 A breaker. 14 AWG is limited to 15 A, so it can never go on a 20 A breaker. 10 AWG on a 20 A breaker is always allowed: bigger wire is never a code problem, only a cost and workmanship one.

Voltage drop by distance

Percent drop at 120 V, one-way distance, copper. 16 A is a heavy continuous load (80% of the breaker); 20 A is the breaker's full rating.

Run12 AWG @ 16 A10 AWG @ 16 A12 AWG @ 20 A10 AWG @ 20 A
25 ft1.3%0.8%1.6%1.0%
50 ft2.6%1.6%3.2%2.0%
75 ft3.9%2.4%4.8%3.0%
100 ft5.1%3.2%6.4%4.0%
150 ft7.7%4.8%9.7%6.1%

Most household 20 A circuits never see 16 A for long, so 12 AWG is fine for a typical kitchen or bathroom run. It's the long, heavily loaded runs where 10 AWG pays off: a detached garage or shed, a workshop with a table saw or compressor, or an outdoor circuit feeding a heater.

The downsides of 10 AWG

  • Cost: 10/2 NM-B costs roughly 1.5–1.7× as much as 12/2 per foot.
  • Fit: 10 AWG is stiff, fills boxes faster (box-fill counts 2.5 in³ per conductor vs. 2.25 for 12 AWG) and is awkward on receptacle screw terminals. Backstab holes don't accept it at all.
  • A common trick: run 10 AWG for the long home run, then pigtail to 12 AWG at the first box. The breaker still protects 12 AWG properly.

Check your own run

Keep reading

Sources: NFPA 70 (NEC). Method and tables: methodology.