Size the wire by ampacity first, from NEC Table 310.16 in the column your cable type allows (60 °C for NM-B and UF), then check voltage drop over the run and go up a size if it exceeds 3%. A 20 A circuit uses 12 AWG copper; a 30 A circuit, 10 AWG.

Updated by Biel Vazquez · Sources · How we calculate · Safety

More options: voltage-drop limit and phase

10 AWGcopper, NM-B cable (Romex), indoors

Design current
20.0 A
Breaker
20 A
Smallest size by ampacity
12 AWG (20 A, 60 °C column)
Voltage drop over 50 ft
2.42 V = 2.02%

Check: Upsized from 12 AWG to 10 AWG to keep voltage drop under 3%. The breaker stays at 20 A.

How the wire size is chosen

  1. Design current. The load in amps, or 125% of it for a continuous load (NEC 210.19(A)(1) and 215.2).
  2. Breaker. The next standard size up from the design current (NEC 240.6(A)).
  3. Ampacity. The smallest conductor whose ampacity in Table 310.16 covers the design current, in the temperature column your wiring method allows, and that the breaker is allowed to protect: 14 AWG copper is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A (NEC 240.4(D)), and a breaker one standard size above the wire's ampacity is permitted otherwise (240.4(B)).
  4. Voltage drop. If the run drops more than your limit, step up until it doesn't, using resistance from NEC Chapter 9, Table 8.

The column rule most wire charts skip

Table 310.16 lists three ampacities per size: 60 °C, 75 °C and 90 °C. You may not just read the biggest one. NM-B cable (Romex) is limited to the 60 °C column by NEC 334.80, even though its conductors are rated 90 °C. UF cable is limited the same way (340.80). Individual THHN wires in conduit can use the 75 °C column only when both ends terminate on equipment rated 75 °C, which most modern breakers and panels are; circuits of 100 A or less default to 60 °C otherwise (110.14(C)).

That is why a 50 A range circuit in NM-B needs 6 AWG, while the same circuit in THHN through conduit can use 8 AWG. More in the 60 °C rule, explained.

Wire size chart by breaker

Computed from Table 310.16 for runs short enough that voltage drop doesn't apply. "NM-B" means the 60 °C column; "THHN 75 °C" means conduit with 75 °C terminations.

BreakerCopper NM-BCopper THHN 75 °CAluminum NM/SE 60 °CAluminum 75 °C
15 A14 AWG14 AWG12 AWG12 AWG
20 A12 AWG12 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG8 AWG
40 A8 AWG8 AWG6 AWG8 AWG
50 A6 AWG8 AWG4 AWG6 AWG
60 A4 AWG6 AWG3 AWG4 AWG
70 A4 AWG4 AWG2 AWG3 AWG
80 A3 AWG4 AWG1 AWG2 AWG
90 A2 AWG3 AWG1/0 AWG2 AWG
100 A1 AWG3 AWG1/0 AWG1 AWG
125 A1/0 AWG1 AWG3/0 AWG2/0 AWG
150 A3/0 AWG1/0 AWG4/0 AWG3/0 AWG
200 A250 kcmil3/0 AWG350 kcmil250 kcmil

When distance changes the answer

A 20 A, 120 V circuit running 150 ft to a detached garage passes on ampacity with 12 AWG, but drops more than 3% at full load. The calculator steps it up to 6 AWG (2.5% drop). The breaker stays at 20 A; only the wire gets bigger. Check any run with the voltage drop calculator.

What this calculator does not cover

  • More than three current-carrying conductors in one raceway or cable bundle (derate per 310.15(C)(1)).
  • Ambient temperatures above 86 °F, such as attics and rooftop conduit (correct per 310.15(B)).
  • Motor circuits, which follow Article 430, and service and feeder sizing for dwellings (310.12).

Safety. Turn off the breaker and verify with a tester before touching any conductor. Most US jurisdictions require a permit for new circuits, and some only allow homeowners to wire their own single-family home. When in doubt, hire a licensed electrician.

Common questions

What size wire for a 20 amp circuit?

12 AWG copper. 14 AWG is not allowed on a 20 A breaker (NEC 240.4(D)). On runs over about 100 ft at full load, 10 AWG keeps voltage drop under 3%. 10 vs 12 gauge, compared.

What size wire for a 50 amp circuit?

6 AWG copper in NM-B cable. With THHN in conduit and 75 °C terminations, 8 AWG copper is allowed. Aluminum: 4 AWG in SE/NM-type cable, 6 AWG at 75 °C.

What size wire for a 30 amp circuit?

10 AWG copper, in NM-B or THHN. A 30 A dryer or water heater circuit is the classic 10/2 or 10/3 run.

Can I use aluminum wire?

Modern AA-8000 aluminum is common and code-compliant for feeders and larger circuits (typically 8 AWG and up). Use terminals rated AL or CU/AL, an anti-oxidant where the manufacturer calls for it, and torque to spec. Avoid small-gauge aluminum branch circuits.

Guides that use this calculator

Updated by Biel Vazquez · Source: NEC Table 310.16 (2023)