Wire & Watts

Wiring

Breaker size calculator

Convert the load to amps (watts ÷ volts). If it runs 3 hours or more, multiply by 1.25. Then pick the next standard breaker size up. A 1,500 W heater at 120 V draws 12.5 A, which becomes 15.6 A, so it needs a 20 A breaker and 12 AWG wire.

Updated by Biel Vazquez · Sources · How we calculate · Safety

I know the load in

20 Abreaker at 120 V

Load current
12.5 A (1,500 W)
Sizing current
15.6 A = 125% for a continuous load
Breaker loaded to
63%
Copper NM-B (Romex)
12 AWG
Copper THHN, 75 °C
12 AWG

Plug-in appliances on a shared circuit: one appliance on a cord should not exceed 80% of a 15 or 20 A circuit (NEC 210.23).

The rule

amps        = watts ÷ volts
sizing amps = amps × 1.25   (continuous load, 3 h or more)
breaker     = next standard size ≥ sizing amps   (NEC 240.6(A))

A breaker protects the wire, not the appliance. It has to be big enough not to trip under normal load, and small enough that the wire behind it can never carry more than it is rated for. Standard breaker sizes are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90 and 100 A, then larger steps.

The 125% rule exists because breakers and terminals heat up under sustained load. A load that runs three hours or more must not exceed 80% of the breaker's rating — which is the same as sizing the breaker at 125% of the load (NEC 210.20(A)). Water heaters (422.13), EV chargers (625.41) and fixed electric space heating (424.4) are treated as continuous by rule.

Common household loads

LoadWattsVoltsAmpsContinuousBreakerCopper NM-B
Space heater1,500120 V12.5yes20 A12 AWG
Microwave1,200120 V10.0no15 A14 AWG
Window AC 12,000 BTU1,100120 V9.2no15 A14 AWG
Water heater 4,500 W4,500240 V18.8yes25 A10 AWG
Water heater 5,500 W5,500240 V22.9yes30 A10 AWG
Electric dryer5,400240 V22.5no25 A10 AWG
Electric range9,600240 V40.0no40 A8 AWG
Baseboard heat 2,500 W2,500240 V10.4yes15 A14 AWG
Hot tub7,200240 V30.0yes40 A8 AWG
Mini split 18,000 BTU1,900240 V7.9no15 A14 AWG

Always use the nameplate and the installation manual when you have them. Many appliances state a "maximum overcurrent protection" (MOP) or minimum circuit ampacity (MCA) — air conditioners and heat pumps in particular — and that number overrides any calculation.

Can I just put in a bigger breaker?

No. If a 15 A circuit keeps tripping, swapping in a 20 A breaker on 14 AWG wire removes the protection that keeps the wire from overheating inside your walls. Either reduce the load on the circuit or run a new circuit sized for it.

Safety. Working inside a panel is dangerous even with the main breaker off: the service conductors above it stay live. Leave panel work to a licensed electrician unless you are trained for it.

Common questions

What size breaker for a 1,500 W space heater?

20 A at 120 V. It draws 12.5 A; as a continuous load that becomes 15.6 A, over a 15 A breaker's limit.

What size breaker for a 4,500 W water heater?

30 A double-pole at 240 V with 10 AWG copper. 4,500 W ÷ 240 V = 18.75 A × 1.25 = 23.4 A, rounded up to 25 A minimum; 30 A is the usual choice with 10 AWG.

How many watts can a 20 amp breaker handle?

2,400 W at 120 V for short loads, 1,920 W continuous (80%). At 240 V, 4,800 W and 3,840 W.

Guides that use this calculator

Updated by Biel Vazquez · Source: NEC Table 310.16 (2023)

Related calculators