What size wire for a 70 amp breaker?
Short answer: A 70 A breaker needs at least 4 AWG copper or 3 AWG aluminum as individual wires in conduit with 75 °C terminations, or 4 AWG copper in NM-B (Romex) cable, which is held to the 60 °C column. Long runs need a bigger size to keep voltage drop under 3%.
Minimum wire size for 70 A by wire type
| Wire type | Minimum size | Ampacity (NEC 310.16) |
|---|---|---|
| Copper NM-B (Romex) | 4 AWG | 70 A |
| Copper THHN/THWN-2 in conduit, 75 °C | 4 AWG | 85 A |
| Aluminum SER / NM-B (60 °C) | 2 AWG | 75 A |
| Aluminum XHHW-2 in conduit, 75 °C | 3 AWG | 75 A |
The column matters as much as the breaker. NEC 334.80 limits NM-B cable to its 60 °C ampacity, so the same 70 A breaker needs a larger gauge in Romex than in conduit. Individual THHN or XHHW-2 wires can use the 75 °C column, but only when both ends terminate on lugs rated 75 °C, which is true of nearly all residential breakers and panels sold today but should be checked on the label. NEC 240.4(B) also lets you protect a wire with the next standard breaker above its ampacity (up to 800 A) when the load itself fits the wire, which is how 70 A breakers end up on some sizes listed one step smaller in other charts.
When distance pushes the size up
Smallest size that is both legal for the 70 A breaker and keeps voltage drop at or under 3% at 240 V, with a load of 56 A (80% of the breaker):
| One-way length | Copper, 75 °C | Aluminum, 75 °C |
|---|---|---|
| 50 ft | 4 AWG (0.7%) | 3 AWG (0.9%) |
| 100 ft | 4 AWG (1.4%) | 3 AWG (1.9%) |
| 150 ft | 4 AWG (2.2%) | 3 AWG (2.8%) |
| 200 ft | 4 AWG (2.9%) | 2 AWG (3.0%) |
| 300 ft | 2 AWG (2.7%) | 1/0 AWG (2.8%) |
Upsizing for distance does not change the breaker. It does change the ground: NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion when the hot conductors are upsized for voltage drop.
Ground wire for a 70 A circuit
NEC Table 250.122 sizes the equipment ground from the breaker: 8 AWG copper or 6 AWG aluminum for 70 A. Cable assemblies (NM-B, SER, UF) include a ground already sized for their gauge. A 70 A circuit carries up to 16,800 W at 240 V, or 13,440 W for a continuous load.
Common 70 A circuits
- Subpanel where 60 A is too tight for the planned loads.
- Large heat pump or air handler with electric heat strips: check the nameplate MCA and MOCP.
- Two EV chargers sharing a load-managed circuit.
Feeding a subpanel? It needs four wires (two hots, a neutral and a ground), with the neutral and ground kept separate in the subpanel, and a detached building needs its own grounding electrode (NEC 250.32).
Safety. Installing a 70 A circuit or feeder needs a permit almost everywhere in the US. Equipment nameplates (minimum circuit ampacity and maximum overcurrent protection) override any general table, and local amendments to the NEC can be stricter.