Wire & Watts

What size wire for a 80 amp breaker?

Updated by Biel Vazquez

Short answer: A 80 A breaker needs at least 4 AWG copper or 2 AWG aluminum as individual wires in conduit with 75 °C terminations, or 3 AWG copper in NM-B (Romex) cable, which is held to the 60 °C column. Long runs need a bigger size to keep voltage drop under 3%.

Minimum wire size for 80 A by wire type

For a 80 A load on a 80 A breaker, 30 °C ambient, no more than three current-carrying conductors.
Wire typeMinimum sizeAmpacity (NEC 310.16)
Copper NM-B (Romex)3 AWG85 A
Copper THHN/THWN-2 in conduit, 75 °C4 AWG85 A
Aluminum SER / NM-B (60 °C)1 AWG85 A
Aluminum XHHW-2 in conduit, 75 °C2 AWG90 A

The column matters as much as the breaker. NEC 334.80 limits NM-B cable to its 60 °C ampacity, so the same 80 A breaker needs a larger gauge in Romex than in conduit. Individual THHN or XHHW-2 wires can use the 75 °C column, but only when both ends terminate on lugs rated 75 °C, which is true of nearly all residential breakers and panels sold today but should be checked on the label. NEC 240.4(B) also lets you protect a wire with the next standard breaker above its ampacity (up to 800 A) when the load itself fits the wire, which is how 80 A breakers end up on some sizes listed one step smaller in other charts.

When distance pushes the size up

Smallest size that is both legal for the 80 A breaker and keeps voltage drop at or under 3% at 240 V, with a load of 64 A (80% of the breaker):

Resistance from NEC Chapter 9, Table 8. Length is one way; the current travels out and back.
One-way lengthCopper, 75 °CAluminum, 75 °C
50 ft4 AWG (0.8%)2 AWG (0.9%)
100 ft4 AWG (1.6%)2 AWG (1.7%)
150 ft4 AWG (2.5%)2 AWG (2.6%)
200 ft3 AWG (2.6%)1 AWG (2.7%)
300 ft1 AWG (2.5%)2/0 AWG (2.5%)

Upsizing for distance does not change the breaker. It does change the ground: NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion when the hot conductors are upsized for voltage drop.

Ground wire for a 80 A circuit

NEC Table 250.122 sizes the equipment ground from the breaker: 8 AWG copper or 6 AWG aluminum for 80 A. Cable assemblies (NM-B, SER, UF) include a ground already sized for their gauge. A 80 A circuit carries up to 19,200 W at 240 V, or 15,360 W for a continuous load.

Common 80 A circuits

  • 80 A Level 2 EV chargers are 64 A continuous, which needs an 80 A breaker (64 × 1.25), 4 AWG copper THHN or 3 AWG NM-B.
  • Subpanel for a detached garage or ADU.
  • Air handler with 15–20 kW heat strips.

Feeding a subpanel? It needs four wires (two hots, a neutral and a ground), with the neutral and ground kept separate in the subpanel, and a detached building needs its own grounding electrode (NEC 250.32).

Size wire for your run

Safety. Installing a 80 A circuit or feeder needs a permit almost everywhere in the US. Equipment nameplates (minimum circuit ampacity and maximum overcurrent protection) override any general table, and local amendments to the NEC can be stricter.

Keep reading

Sources: NFPA 70 (NEC). Method and tables: methodology.