Wire & Watts

What size wire for a 100 amp breaker?

Updated by Biel Vazquez

Short answer: A 100 A breaker needs at least 3 AWG copper or 1 AWG aluminum as individual wires in conduit with 75 °C terminations, or 1 AWG copper in NM-B (Romex) cable, which is held to the 60 °C column. Long runs need a bigger size to keep voltage drop under 3%. For a 100 A dwelling service or main feeder, NEC 310.12 allows 4 AWG copper or 2 AWG aluminum.

Minimum wire size for 100 A by wire type

For a 100 A load on a 100 A breaker, 30 °C ambient, no more than three current-carrying conductors.
Wire typeMinimum sizeAmpacity (NEC 310.16)
Copper NM-B (Romex)1 AWG110 A
Copper THHN/THWN-2 in conduit, 75 °C3 AWG100 A
Aluminum SER / NM-B (60 °C)1/0 AWG100 A
Aluminum XHHW-2 in conduit, 75 °C1 AWG100 A

The column matters as much as the breaker. NEC 334.80 limits NM-B cable to its 60 °C ampacity, so the same 100 A breaker needs a larger gauge in Romex than in conduit. Individual THHN or XHHW-2 wires can use the 75 °C column, but only when both ends terminate on lugs rated 75 °C, which is true of nearly all residential breakers and panels sold today but should be checked on the label. NEC 240.4(B) also lets you protect a wire with the next standard breaker above its ampacity (up to 800 A) when the load itself fits the wire, which is how 100 A breakers end up on some sizes listed one step smaller in other charts.

When distance pushes the size up

Smallest size that is both legal for the 100 A breaker and keeps voltage drop at or under 3% at 240 V, with a load of 80 A (80% of the breaker):

Resistance from NEC Chapter 9, Table 8. Length is one way; the current travels out and back.
One-way lengthCopper, 75 °CAluminum, 75 °C
50 ft3 AWG (0.8%)1 AWG (0.8%)
100 ft3 AWG (1.6%)1 AWG (1.7%)
150 ft3 AWG (2.5%)1 AWG (2.5%)
200 ft2 AWG (2.6%)1/0 AWG (2.7%)
300 ft1/0 AWG (2.4%)3/0 AWG (2.5%)

Upsizing for distance does not change the breaker. It does change the ground: NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion when the hot conductors are upsized for voltage drop.

100 A service or main feeder: the 83% rule

For a 120/240 V single-phase dwelling, NEC 310.12 lets service-entrance conductors, and a feeder that carries the whole load of the house, be sized at 83% of the service rating: 83.0 A for a 100 A service. That is why a 100 A service is commonly wired with:

MaterialSizeAmpacity at 75 °C
Copper4 AWG85 A
Aluminum2 AWG90 A

The rule does not apply to a subpanel feeder that carries only part of the house's load. A 100 A subpanel uses the full table above.

Ground wire for a 100 A circuit

NEC Table 250.122 sizes the equipment ground from the breaker: 8 AWG copper or 6 AWG aluminum for 100 A. Cable assemblies (NM-B, SER, UF) include a ground already sized for their gauge. A 100 A circuit carries up to 24,000 W at 240 V, or 19,200 W for a continuous load.

Common 100 A circuits

  • 100 A subpanel in a garage, basement or detached building: the most common feeder size.
  • 100 A service for a small home, where NEC 310.12 lets the service conductors be smaller (see below).
  • Large electric furnace or whole-house tankless heater fed from its own disconnect.

Feeding a subpanel? It needs four wires (two hots, a neutral and a ground), with the neutral and ground kept separate in the subpanel, and a detached building needs its own grounding electrode (NEC 250.32).

Size wire for your run

Safety. Installing a 100 A circuit or feeder needs a permit almost everywhere in the US. Equipment nameplates (minimum circuit ampacity and maximum overcurrent protection) override any general table, and local amendments to the NEC can be stricter.

Keep reading

Sources: NFPA 70 (NEC). Method and tables: methodology.