Wire & Watts

What size wire for 100 amps at 200 feet?

Updated by Biel Vazquez

Short answer: For a 100 amp load 200 feet away (one way) at 240 V, use 1 AWG copper or 2/0 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.6% and 2.7%. In NM-B (Romex) cable it is 1 AWG copper. The breaker stays 100 A; the extra size is only for distance.

100 amps at 200 feet: wire size by type

240 V single phase, 100 A load on a 100 A breaker, 200 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 200 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C3 AWG1 AWG2.57%
Aluminum XHHW-2 in conduit, 75 °C1 AWG2/0 AWG2.65%
Copper NM-B (Romex) cable, 60 °C1 AWG1 AWG2.57%
Aluminum SER / NM-B cable, 60 °C1/0 AWG2/0 AWG2.65%

That is one or more sizes above the 3 AWG that ampacity alone allows: at 200 ft the run, not the breaker, decides the gauge. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 8 AWG copper for a 100 A breaker.

Voltage drop of each gauge over 200 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 100 ADrop at 100 ADrop at 80 A (80%)
3 AWG copper9.80 V4.08%3.27%
2 AWG copper7.76 V3.23%2.59%
1 AWG copper6.16 V2.57%2.05%
1/0 AWG copper4.88 V2.03%1.63%
2/0 AWG copper3.87 V1.61%1.29%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 200 × R(1 AWG) × 100 ÷ 1,000 = 6.16 V
percent     = 6.16 ÷ 240 × 100 = 2.57%

If the real load is the 80% continuous maximum (80 A, as with an EV charger on a 100 A breaker), copper in conduit can be 2 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 100 A, other distances

50 ft · 75 ft · 100 ft · 150 ft. Minimum sizes with no distance correction: what size wire for a 100 amp breaker.

Other loads at 200 feet

30 A · 40 A · 50 A · 60 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 100 A circuit or feeder over 200 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.

Keep reading

Sources: NFPA 70 (NEC), NEC Chapter 9, Table 8: conductor properties. Method and tables: methodology.