What size wire for 50 amps at 200 feet?
Short answer: For a 50 amp load 200 feet away (one way) at 240 V, use 4 AWG copper or 2 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.6% and 2.7%. In NM-B (Romex) cable it is 4 AWG copper. The breaker stays 50 A; the extra size is only for distance.
50 amps at 200 feet: wire size by type
| Wire type | Size by ampacity | Size for 200 ft (≤3% drop) | Voltage drop |
|---|---|---|---|
| Copper THHN/THWN-2 in conduit, 75 °C | 8 AWG | 4 AWG | 2.57% |
| Aluminum XHHW-2 in conduit, 75 °C | 6 AWG | 2 AWG | 2.66% |
| Copper NM-B (Romex) cable, 60 °C | 6 AWG | 4 AWG | 2.57% |
| Aluminum SER / NM-B cable, 60 °C | 4 AWG | 2 AWG | 2.66% |
That is one or more sizes above the 8 AWG that ampacity alone allows: at 200 ft the run, not the breaker, decides the gauge. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 50 A breaker.
At 120 volts
The same 50 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:
| Wire type | Size for 200 ft | Voltage drop |
|---|---|---|
| Copper THHN/THWN-2 in conduit, 75 °C | 1 AWG | 2.57% |
| Aluminum XHHW-2 in conduit, 75 °C | 2/0 AWG | 2.65% |
Voltage drop of each gauge over 200 ft
| Wire | Volts lost at 50 A | Drop at 50 A | Drop at 40 A (80%) |
|---|---|---|---|
| 8 AWG copper | 15.28 V | 6.37% | 5.09% |
| 6 AWG copper | 9.82 V | 4.09% | 3.27% |
| 4 AWG copper | 6.16 V | 2.57% | 2.05% |
| 3 AWG copper | 4.90 V | 2.04% | 1.63% |
| 2 AWG copper | 3.88 V | 1.62% | 1.29% |
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
= 2 × 200 × R(4 AWG) × 50 ÷ 1,000 = 6.16 V
percent = 6.16 ÷ 240 × 100 = 2.57%
If the real load is the 80% continuous maximum (40 A, as with an EV charger on a 50 A breaker), copper in conduit can be 4 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.