What size wire for 50 amps at 50 feet?

Updated by Biel Vazquez

Short answer: For a 50 amp load 50 feet away (one way) at 240 V, use 8 AWG copper or 6 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 1.6% and 1.7%. In NM-B (Romex) cable it is 6 AWG copper. The breaker stays 50 A; distance does not force a larger size.

50 amps at 50 feet: wire size by type

240 V single phase, 50 A load on a 50 A breaker, 50 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 50 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C8 AWG8 AWG1.59%
Aluminum XHHW-2 in conduit, 75 °C6 AWG6 AWG1.68%
Copper NM-B (Romex) cable, 60 °C6 AWG6 AWG1.02%
Aluminum SER / NM-B cable, 60 °C4 AWG4 AWG1.06%

At 50 ft, voltage drop stays under 3% with the ampacity size, so distance does not force a bigger wire. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 50 A breaker.

At 120 volts

The same 50 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:

Wire typeSize for 50 ftVoltage drop
Copper THHN/THWN-2 in conduit, 75 °C6 AWG2.05%
Aluminum XHHW-2 in conduit, 75 °C4 AWG2.12%

Voltage drop of each gauge over 50 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 50 ADrop at 50 ADrop at 40 A (80%)
8 AWG copper3.82 V1.59%1.27%
6 AWG copper2.46 V1.02%0.82%
4 AWG copper1.54 V0.64%0.51%
3 AWG copper1.23 V0.51%0.41%
2 AWG copper0.97 V0.40%0.32%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 50 × R(8 AWG) × 50 ÷ 1,000 = 3.82 V
percent     = 3.82 ÷ 240 × 100 = 1.59%

If the real load is the 80% continuous maximum (40 A, as with an EV charger on a 50 A breaker), copper in conduit can be 8 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 50 A, other distances

75 ft · 100 ft · 150 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 50 amp breaker.

Other loads at 50 feet

30 A · 40 A · 60 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 50 A circuit or feeder over 50 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.

Keep reading

Sources: NFPA 70 (NEC), NEC Chapter 9, Table 8: conductor properties. Method and tables: methodology.