What size wire for 125 amps at 50 feet?

Updated by Biel Vazquez

Short answer: For a 125 amp load 50 feet away (one way) at 240 V, use 1 AWG copper or 2/0 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 0.8% and 0.8%. In NM-B (Romex) cable it is 1/0 AWG copper. The breaker stays 125 A; distance does not force a larger size.

125 amps at 50 feet: wire size by type

240 V single phase, 125 A load on a 125 A breaker, 50 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 50 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C1 AWG1 AWG0.80%
Aluminum XHHW-2 in conduit, 75 °C2/0 AWG2/0 AWG0.83%
Copper NM-B (Romex) cable, 60 °C1/0 AWG1/0 AWG0.64%
Aluminum SER / NM-B cable, 60 °C3/0 AWG3/0 AWG0.66%

At 50 ft, voltage drop stays under 3% with the ampacity size, so distance does not force a bigger wire. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 6 AWG copper for a 125 A breaker.

Voltage drop of each gauge over 50 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 125 ADrop at 125 ADrop at 100 A (80%)
1 AWG copper1.93 V0.80%0.64%
1/0 AWG copper1.53 V0.64%0.51%
2/0 AWG copper1.21 V0.50%0.40%
3/0 AWG copper0.96 V0.40%0.32%
4/0 AWG copper0.76 V0.32%0.25%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 50 × R(1 AWG) × 125 ÷ 1,000 = 1.93 V
percent     = 1.93 ÷ 240 × 100 = 0.80%

If the real load is the 80% continuous maximum (100 A, as with an EV charger on a 125 A breaker), copper in conduit can be 3 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 125 A, other distances

75 ft · 100 ft · 150 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 125 amp breaker.

Other loads at 50 feet

30 A · 40 A · 50 A · 60 A · 100 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 125 A circuit or feeder over 50 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.