What size wire for 30 amps at 50 feet?
Short answer: For a 30 amp load 50 feet away (one way) at 240 V, use 10 AWG copper or 8 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 1.5% and 1.6%. In NM-B (Romex) cable it is 10 AWG copper. The breaker stays 30 A; distance does not force a larger size.
30 amps at 50 feet: wire size by type
| Wire type | Size by ampacity | Size for 50 ft (≤3% drop) | Voltage drop |
|---|---|---|---|
| Copper THHN/THWN-2 in conduit, 75 °C | 10 AWG | 10 AWG | 1.51% |
| Aluminum XHHW-2 in conduit, 75 °C | 8 AWG | 8 AWG | 1.58% |
| Copper NM-B (Romex) cable, 60 °C | 10 AWG | 10 AWG | 1.51% |
| Aluminum SER / NM-B cable, 60 °C | 8 AWG | 8 AWG | 1.58% |
At 50 ft, voltage drop stays under 3% with the ampacity size, so distance does not force a bigger wire. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 30 A breaker.
At 120 volts
The same 30 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:
| Wire type | Size for 50 ft | Voltage drop |
|---|---|---|
| Copper THHN/THWN-2 in conduit, 75 °C | 8 AWG | 1.91% |
| Aluminum XHHW-2 in conduit, 75 °C | 6 AWG | 2.02% |
Voltage drop of each gauge over 50 ft
| Wire | Volts lost at 30 A | Drop at 30 A | Drop at 24 A (80%) |
|---|---|---|---|
| 10 AWG copper | 3.63 V | 1.51% | 1.21% |
| 8 AWG copper | 2.29 V | 0.96% | 0.76% |
| 6 AWG copper | 1.47 V | 0.61% | 0.49% |
| 4 AWG copper | 0.92 V | 0.39% | 0.31% |
| 3 AWG copper | 0.74 V | 0.31% | 0.25% |
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
= 2 × 50 × R(10 AWG) × 30 ÷ 1,000 = 3.63 V
percent = 3.63 ÷ 240 × 100 = 1.51%
If the real load is the 80% continuous maximum (24 A, as with an EV charger on a 30 A breaker), copper in conduit can be 10 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.