Wire & Watts

What size wire for 30 amps at 50 feet?

Updated by Biel Vazquez

Short answer: For a 30 amp load 50 feet away (one way) at 240 V, use 10 AWG copper or 8 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 1.5% and 1.6%. In NM-B (Romex) cable it is 10 AWG copper. The breaker stays 30 A; distance does not force a larger size.

30 amps at 50 feet: wire size by type

240 V single phase, 30 A load on a 30 A breaker, 50 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 50 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C10 AWG10 AWG1.51%
Aluminum XHHW-2 in conduit, 75 °C8 AWG8 AWG1.58%
Copper NM-B (Romex) cable, 60 °C10 AWG10 AWG1.51%
Aluminum SER / NM-B cable, 60 °C8 AWG8 AWG1.58%

At 50 ft, voltage drop stays under 3% with the ampacity size, so distance does not force a bigger wire. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 30 A breaker.

At 120 volts

The same 30 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:

Wire typeSize for 50 ftVoltage drop
Copper THHN/THWN-2 in conduit, 75 °C8 AWG1.91%
Aluminum XHHW-2 in conduit, 75 °C6 AWG2.02%

Voltage drop of each gauge over 50 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 30 ADrop at 30 ADrop at 24 A (80%)
10 AWG copper3.63 V1.51%1.21%
8 AWG copper2.29 V0.96%0.76%
6 AWG copper1.47 V0.61%0.49%
4 AWG copper0.92 V0.39%0.31%
3 AWG copper0.74 V0.31%0.25%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 50 × R(10 AWG) × 30 ÷ 1,000 = 3.63 V
percent     = 3.63 ÷ 240 × 100 = 1.51%

If the real load is the 80% continuous maximum (24 A, as with an EV charger on a 30 A breaker), copper in conduit can be 10 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 30 A, other distances

75 ft · 100 ft · 150 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 30 amp breaker.

Other loads at 50 feet

40 A · 50 A · 60 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 30 A circuit or feeder over 50 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.

Keep reading

Sources: NFPA 70 (NEC), NEC Chapter 9, Table 8: conductor properties. Method and tables: methodology.