What size wire for 30 amps at 150 feet?

Updated by Biel Vazquez

Short answer: For a 30 amp load 150 feet away (one way) at 240 V, use 8 AWG copper or 4 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.9% and 1.9%. In NM-B (Romex) cable it is 8 AWG copper. The breaker stays 30 A; the extra size is only for distance.

30 amps at 150 feet: wire size by type

240 V single phase, 30 A load on a 30 A breaker, 150 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 150 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C10 AWG8 AWG2.87%
Aluminum XHHW-2 in conduit, 75 °C8 AWG4 AWG1.91%
Copper NM-B (Romex) cable, 60 °C10 AWG8 AWG2.87%
Aluminum SER / NM-B cable, 60 °C8 AWG4 AWG1.91%

That is one or more sizes above the 10 AWG that ampacity alone allows: at 150 ft the run, not the breaker, decides the gauge. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 30 A breaker.

At 120 volts

The same 30 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:

Wire typeSize for 150 ftVoltage drop
Copper THHN/THWN-2 in conduit, 75 °C4 AWG2.31%
Aluminum XHHW-2 in conduit, 75 °C2 AWG2.39%

Voltage drop of each gauge over 150 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 30 ADrop at 30 ADrop at 24 A (80%)
10 AWG copper10.89 V4.54%3.63%
8 AWG copper6.88 V2.87%2.29%
6 AWG copper4.42 V1.84%1.47%
4 AWG copper2.77 V1.16%0.92%
3 AWG copper2.21 V0.92%0.74%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 150 × R(8 AWG) × 30 ÷ 1,000 = 6.88 V
percent     = 6.88 ÷ 240 × 100 = 2.87%

If the real load is the 80% continuous maximum (24 A, as with an EV charger on a 30 A breaker), copper in conduit can be 8 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 30 A, other distances

50 ft · 75 ft · 100 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 30 amp breaker.

Other loads at 150 feet

40 A · 50 A · 60 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 30 A circuit or feeder over 150 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.

Keep reading