What size wire for 50 amps at 150 feet?

Updated by Biel Vazquez

Short answer: For a 50 amp load 150 feet away (one way) at 240 V, use 4 AWG copper or 3 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 1.9% and 2.5%. In NM-B (Romex) cable it is 4 AWG copper. The breaker stays 50 A; the extra size is only for distance.

50 amps at 150 feet: wire size by type

240 V single phase, 50 A load on a 50 A breaker, 150 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 150 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C8 AWG4 AWG1.93%
Aluminum XHHW-2 in conduit, 75 °C6 AWG3 AWG2.52%
Copper NM-B (Romex) cable, 60 °C6 AWG4 AWG1.93%
Aluminum SER / NM-B cable, 60 °C4 AWG3 AWG2.52%

That is one or more sizes above the 8 AWG that ampacity alone allows: at 150 ft the run, not the breaker, decides the gauge. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 50 A breaker.

At 120 volts

The same 50 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:

Wire typeSize for 150 ftVoltage drop
Copper THHN/THWN-2 in conduit, 75 °C2 AWG2.43%
Aluminum XHHW-2 in conduit, 75 °C1/0 AWG2.51%

Voltage drop of each gauge over 150 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 50 ADrop at 50 ADrop at 40 A (80%)
8 AWG copper11.46 V4.78%3.82%
6 AWG copper7.37 V3.07%2.46%
4 AWG copper4.62 V1.93%1.54%
3 AWG copper3.68 V1.53%1.23%
2 AWG copper2.91 V1.21%0.97%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 150 × R(4 AWG) × 50 ÷ 1,000 = 4.62 V
percent     = 4.62 ÷ 240 × 100 = 1.93%

If the real load is the 80% continuous maximum (40 A, as with an EV charger on a 50 A breaker), copper in conduit can be 6 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 50 A, other distances

50 ft · 75 ft · 100 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 50 amp breaker.

Other loads at 150 feet

30 A · 40 A · 60 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 50 A circuit or feeder over 150 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.