What size wire for 60 amps at 150 feet?

Updated by Biel Vazquez

Short answer: For a 60 amp load 150 feet away (one way) at 240 V, use 4 AWG copper or 2 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.3% and 2.4%. In NM-B (Romex) cable it is 4 AWG copper. The breaker stays 60 A; the extra size is only for distance.

60 amps at 150 feet: wire size by type

240 V single phase, 60 A load on a 60 A breaker, 150 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 150 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C6 AWG4 AWG2.31%
Aluminum XHHW-2 in conduit, 75 °C4 AWG2 AWG2.39%
Copper NM-B (Romex) cable, 60 °C4 AWG4 AWG2.31%
Aluminum SER / NM-B cable, 60 °C3 AWG2 AWG2.39%

That is one or more sizes above the 6 AWG that ampacity alone allows: at 150 ft the run, not the breaker, decides the gauge. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 60 A breaker.

Voltage drop of each gauge over 150 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 60 ADrop at 60 ADrop at 48 A (80%)
6 AWG copper8.84 V3.68%2.95%
4 AWG copper5.54 V2.31%1.85%
3 AWG copper4.41 V1.84%1.47%
2 AWG copper3.49 V1.46%1.16%
1 AWG copper2.77 V1.16%0.92%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 150 × R(4 AWG) × 60 ÷ 1,000 = 5.54 V
percent     = 5.54 ÷ 240 × 100 = 2.31%

If the real load is the 80% continuous maximum (48 A, as with an EV charger on a 60 A breaker), copper in conduit can be 6 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 60 A, other distances

50 ft · 75 ft · 100 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 60 amp breaker.

Other loads at 150 feet

30 A · 40 A · 50 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 60 A circuit or feeder over 150 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.

Keep reading

Sources: NFPA 70 (NEC), NEC Chapter 9, Table 8: conductor properties. Method and tables: methodology.