What size wire for a 60 amp breaker?

Updated by Biel Vazquez

Short answer: A 60 A breaker needs at least 6 AWG copper or 4 AWG aluminum as individual wires in conduit with 75 °C terminations, or 4 AWG copper in NM-B (Romex) cable, which is held to the 60 °C column. Long runs need a bigger size to keep voltage drop under 3%.

Minimum wire size for 60 A by wire type

For a 60 A load on a 60 A breaker, 30 °C ambient, no more than three current-carrying conductors.
Wire typeMinimum sizeAmpacity (NEC 310.16)
Copper NM-B (Romex)4 AWG70 A
Copper THHN/THWN-2 in conduit, 75 °C6 AWG65 A
Aluminum SER / NM-B (60 °C)3 AWG65 A
Aluminum XHHW-2 in conduit, 75 °C4 AWG65 A

The column matters as much as the breaker. NEC 334.80 limits NM-B cable to its 60 °C ampacity, so the same 60 A breaker needs a larger gauge in Romex than in conduit. Individual THHN or XHHW-2 wires can use the 75 °C column, but only when both ends terminate on lugs rated 75 °C, which is true of nearly all residential breakers and panels sold today but should be checked on the label. NEC 240.4(B) also lets you protect a wire with the next standard breaker above its ampacity (up to 800 A) when the load itself fits the wire, which is how 60 A breakers end up on some sizes listed one step smaller in other charts.

When distance pushes the size up

Smallest size that is both legal for the 60 A breaker and keeps voltage drop at or under 3% at 240 V, with a load of 48 A (80% of the breaker):

Resistance from NEC Chapter 9, Table 8. Length is one way; the current travels out and back.
One-way lengthCopper, 75 °CAluminum, 75 °C
50 ft6 AWG (1.0%)4 AWG (1.0%)
100 ft6 AWG (2.0%)4 AWG (2.0%)
150 ft6 AWG (2.9%)3 AWG (2.4%)
200 ft4 AWG (2.5%)2 AWG (2.6%)
300 ft3 AWG (2.9%)1/0 AWG (2.4%)

Upsizing for distance does not change the breaker. It does change the ground: NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion when the hot conductors are upsized for voltage drop.

Ground wire for a 60 A circuit

NEC Table 250.122 sizes the equipment ground from the breaker: 10 AWG copper or 8 AWG aluminum for 60 A. Cable assemblies (NM-B, SER, UF) include a ground already sized for their gauge. A 60 A circuit carries up to 14,400 W at 240 V, or 11,520 W for a continuous load.

Common 60 A circuits

  • 48 A Level 2 EV charger (hard-wired): 60 A circuit, 4 AWG copper NM-B or 6 AWG THHN at 75 °C.
  • Garage or workshop subpanel: 6/3 copper feeder is the usual starting point.
  • Electric tankless water heater: whole-house models often need two or three 40–60 A circuits.
  • Hot tub / spa: many 240 V spas call for a 50–60 A GFCI disconnect.

Feeding a subpanel? It needs four wires (two hots, a neutral and a ground), with the neutral and ground kept separate in the subpanel, and a detached building needs its own grounding electrode (NEC 250.32).

Size wire for your run

Safety. Installing a 60 A circuit or feeder needs a permit almost everywhere in the US. Equipment nameplates (minimum circuit ampacity and maximum overcurrent protection) override any general table, and local amendments to the NEC can be stricter.