What size wire for 50 amps at 75 feet?

Updated by Biel Vazquez

Short answer: For a 50 amp load 75 feet away (one way) at 240 V, use 8 AWG copper or 6 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.4% and 2.5%. In NM-B (Romex) cable it is 6 AWG copper. The breaker stays 50 A; distance does not force a larger size.

50 amps at 75 feet: wire size by type

240 V single phase, 50 A load on a 50 A breaker, 75 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 75 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C8 AWG8 AWG2.39%
Aluminum XHHW-2 in conduit, 75 °C6 AWG6 AWG2.53%
Copper NM-B (Romex) cable, 60 °C6 AWG6 AWG1.53%
Aluminum SER / NM-B cable, 60 °C4 AWG4 AWG1.59%

At 75 ft, voltage drop stays under 3% with the ampacity size, so distance does not force a bigger wire. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 50 A breaker.

At 120 volts

The same 50 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:

Wire typeSize for 75 ftVoltage drop
Copper THHN/THWN-2 in conduit, 75 °C4 AWG1.93%
Aluminum XHHW-2 in conduit, 75 °C3 AWG2.52%

Voltage drop of each gauge over 75 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 50 ADrop at 50 ADrop at 40 A (80%)
8 AWG copper5.73 V2.39%1.91%
6 AWG copper3.68 V1.53%1.23%
4 AWG copper2.31 V0.96%0.77%
3 AWG copper1.84 V0.77%0.61%
2 AWG copper1.46 V0.61%0.48%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 75 × R(8 AWG) × 50 ÷ 1,000 = 5.73 V
percent     = 5.73 ÷ 240 × 100 = 2.39%

If the real load is the 80% continuous maximum (40 A, as with an EV charger on a 50 A breaker), copper in conduit can be 8 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 50 A, other distances

50 ft · 100 ft · 150 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 50 amp breaker.

Other loads at 75 feet

30 A · 40 A · 60 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 50 A circuit or feeder over 75 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.