What size wire for 50 amps at 75 feet?
Short answer: For a 50 amp load 75 feet away (one way) at 240 V, use 8 AWG copper or 6 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.4% and 2.5%. In NM-B (Romex) cable it is 6 AWG copper. The breaker stays 50 A; distance does not force a larger size.
50 amps at 75 feet: wire size by type
| Wire type | Size by ampacity | Size for 75 ft (≤3% drop) | Voltage drop |
|---|---|---|---|
| Copper THHN/THWN-2 in conduit, 75 °C | 8 AWG | 8 AWG | 2.39% |
| Aluminum XHHW-2 in conduit, 75 °C | 6 AWG | 6 AWG | 2.53% |
| Copper NM-B (Romex) cable, 60 °C | 6 AWG | 6 AWG | 1.53% |
| Aluminum SER / NM-B cable, 60 °C | 4 AWG | 4 AWG | 1.59% |
At 75 ft, voltage drop stays under 3% with the ampacity size, so distance does not force a bigger wire. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 50 A breaker.
At 120 volts
The same 50 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:
| Wire type | Size for 75 ft | Voltage drop |
|---|---|---|
| Copper THHN/THWN-2 in conduit, 75 °C | 4 AWG | 1.93% |
| Aluminum XHHW-2 in conduit, 75 °C | 3 AWG | 2.52% |
Voltage drop of each gauge over 75 ft
| Wire | Volts lost at 50 A | Drop at 50 A | Drop at 40 A (80%) |
|---|---|---|---|
| 8 AWG copper | 5.73 V | 2.39% | 1.91% |
| 6 AWG copper | 3.68 V | 1.53% | 1.23% |
| 4 AWG copper | 2.31 V | 0.96% | 0.77% |
| 3 AWG copper | 1.84 V | 0.77% | 0.61% |
| 2 AWG copper | 1.46 V | 0.61% | 0.48% |
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
= 2 × 75 × R(8 AWG) × 50 ÷ 1,000 = 5.73 V
percent = 5.73 ÷ 240 × 100 = 2.39%
If the real load is the 80% continuous maximum (40 A, as with an EV charger on a 50 A breaker), copper in conduit can be 8 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.
Same 50 A, other distances
50 ft · 100 ft · 150 ft · 200 ft. Minimum sizes with no distance correction: what size wire for a 50 amp breaker.
Other loads at 75 feet
30 A · 40 A · 60 A · 100 A · 125 A · 150 A · 200 A
Change the numbers in the calculator
Safety. A 50 A circuit or feeder over 75 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.