What size wire for 30 amps at 200 feet?

Updated by Biel Vazquez

Short answer: For a 30 amp load 200 feet away (one way) at 240 V, use 6 AWG copper or 4 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.5% and 2.5%. In NM-B (Romex) cable it is 6 AWG copper. The breaker stays 30 A; the extra size is only for distance.

30 amps at 200 feet: wire size by type

240 V single phase, 30 A load on a 30 A breaker, 200 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 200 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C10 AWG6 AWG2.46%
Aluminum XHHW-2 in conduit, 75 °C8 AWG4 AWG2.54%
Copper NM-B (Romex) cable, 60 °C10 AWG6 AWG2.46%
Aluminum SER / NM-B cable, 60 °C8 AWG4 AWG2.54%

That is one or more sizes above the 10 AWG that ampacity alone allows: at 200 ft the run, not the breaker, decides the gauge. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 30 A breaker.

At 120 volts

The same 30 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:

Wire typeSize for 200 ftVoltage drop
Copper THHN/THWN-2 in conduit, 75 °C3 AWG2.45%
Aluminum XHHW-2 in conduit, 75 °C1 AWG2.53%

Voltage drop of each gauge over 200 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 30 ADrop at 30 ADrop at 24 A (80%)
10 AWG copper14.52 V6.05%4.84%
8 AWG copper9.17 V3.82%3.06%
6 AWG copper5.89 V2.46%1.96%
4 AWG copper3.70 V1.54%1.23%
3 AWG copper2.94 V1.23%0.98%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 200 × R(6 AWG) × 30 ÷ 1,000 = 5.89 V
percent     = 5.89 ÷ 240 × 100 = 2.46%

If the real load is the 80% continuous maximum (24 A, as with an EV charger on a 30 A breaker), copper in conduit can be 6 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 30 A, other distances

50 ft · 75 ft · 100 ft · 150 ft. Minimum sizes with no distance correction: what size wire for a 30 amp breaker.

Other loads at 200 feet

40 A · 50 A · 60 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 30 A circuit or feeder over 200 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.

Keep reading

Sources: NFPA 70 (NEC), NEC Chapter 9, Table 8: conductor properties. Method and tables: methodology.