What size wire for 40 amps at 200 feet?

Updated by Biel Vazquez

Short answer: For a 40 amp load 200 feet away (one way) at 240 V, use 4 AWG copper or 3 AWG aluminum in conduit with 75 °C terminations, which keeps voltage drop at 2.1% and 2.7%. In NM-B (Romex) cable it is 4 AWG copper. The breaker stays 40 A; the extra size is only for distance.

40 amps at 200 feet: wire size by type

240 V single phase, 40 A load on a 40 A breaker, 200 ft one way, 30 °C ambient. Computed with our wire size calculator.
Wire typeSize by ampacitySize for 200 ft (≤3% drop)Voltage drop
Copper THHN/THWN-2 in conduit, 75 °C8 AWG4 AWG2.05%
Aluminum XHHW-2 in conduit, 75 °C8 AWG3 AWG2.69%
Copper NM-B (Romex) cable, 60 °C8 AWG4 AWG2.05%
Aluminum SER / NM-B cable, 60 °C6 AWG3 AWG2.69%

That is one or more sizes above the 8 AWG that ampacity alone allows: at 200 ft the run, not the breaker, decides the gauge. NEC 250.122(B) then requires the equipment ground to be increased in proportion: start from 10 AWG copper for a 40 A breaker.

At 120 volts

The same 40 A at 120 V loses twice the percentage over the same wire, so long 120 V runs need bigger wire:

Wire typeSize for 200 ftVoltage drop
Copper THHN/THWN-2 in conduit, 75 °C2 AWG2.59%
Aluminum XHHW-2 in conduit, 75 °C1/0 AWG2.68%

Voltage drop of each gauge over 200 ft

Copper, 240 V, resistance from NEC Chapter 9 Table 8 at 75 °C. The current travels out and back, so the wire length is twice the run.
WireVolts lost at 40 ADrop at 40 ADrop at 32 A (80%)
8 AWG copper12.22 V5.09%4.07%
6 AWG copper7.86 V3.27%2.62%
4 AWG copper4.93 V2.05%1.64%
3 AWG copper3.92 V1.63%1.31%
2 AWG copper3.10 V1.29%1.03%
voltage drop = 2 × length × resistance per 1,000 ft × amps ÷ 1,000
            = 2 × 200 × R(4 AWG) × 40 ÷ 1,000 = 4.93 V
percent     = 4.93 ÷ 240 × 100 = 2.05%

If the real load is the 80% continuous maximum (32 A, as with an EV charger on a 40 A breaker), copper in conduit can be 6 AWG. 3% is the NEC's recommendation for a branch circuit (Informational Note to 210.19), not a hard rule, but motors, compressors and chargers run better with it.

Same 40 A, other distances

50 ft · 75 ft · 100 ft · 150 ft. Minimum sizes with no distance correction: what size wire for a 40 amp breaker.

Other loads at 200 feet

30 A · 50 A · 60 A · 100 A · 125 A · 150 A · 200 A

Change the numbers in the calculator

Safety. A 40 A circuit or feeder over 200 ft needs a permit almost everywhere in the US. Buried runs have their own depth and conduit rules (NEC 300.5), and equipment nameplates override any general table.

Keep reading

Sources: NFPA 70 (NEC), NEC Chapter 9, Table 8: conductor properties. Method and tables: methodology.