What size wire for a 200 amp breaker?

Updated by Biel Vazquez

Short answer: A 200 A breaker needs at least 3/0 AWG copper or 250 kcmil aluminum as individual wires in conduit with 75 °C terminations, or 250 kcmil copper in NM-B (Romex) cable, which is held to the 60 °C column. Long runs need a bigger size to keep voltage drop under 3%. For a 200 A dwelling service or main feeder, NEC 310.12 allows 2/0 AWG copper or 4/0 AWG aluminum.

Minimum wire size for 200 A by wire type

For a 200 A load on a 200 A breaker, 30 °C ambient, no more than three current-carrying conductors.
Wire typeMinimum sizeAmpacity (NEC 310.16)
Copper NM-B (Romex)250 kcmil215 A
Copper THHN/THWN-2 in conduit, 75 °C3/0 AWG200 A
Aluminum SER / NM-B (60 °C)350 kcmil210 A
Aluminum XHHW-2 in conduit, 75 °C250 kcmil205 A

The column matters as much as the breaker. NEC 334.80 limits NM-B cable to its 60 °C ampacity, so the same 200 A breaker needs a larger gauge in Romex than in conduit. Individual THHN or XHHW-2 wires can use the 75 °C column, but only when both ends terminate on lugs rated 75 °C, which is true of nearly all residential breakers and panels sold today but should be checked on the label. NEC 240.4(B) also lets you protect a wire with the next standard breaker above its ampacity (up to 800 A) when the load itself fits the wire, which is how 200 A breakers end up on some sizes listed one step smaller in other charts.

When distance pushes the size up

Smallest size that is both legal for the 200 A breaker and keeps voltage drop at or under 3% at 240 V, with a load of 160 A (80% of the breaker):

Resistance from NEC Chapter 9, Table 8. Length is one way; the current travels out and back.
One-way lengthCopper, 75 °CAluminum, 75 °C
50 ft3/0 AWG (0.5%)250 kcmil (0.6%)
100 ft3/0 AWG (1.0%)250 kcmil (1.1%)
150 ft3/0 AWG (1.5%)250 kcmil (1.7%)
200 ft3/0 AWG (2.0%)250 kcmil (2.3%)
300 ft4/0 AWG (2.4%)300 kcmil (2.8%)

Upsizing for distance does not change the breaker. It does change the ground: NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion when the hot conductors are upsized for voltage drop.

200 A service or main feeder: the 83% rule

For a 120/240 V single-phase dwelling, NEC 310.12 lets service-entrance conductors, and a feeder that carries the whole load of the house, be sized at 83% of the service rating: 166.0 A for a 200 A service. That is why a 200 A service is commonly wired with:

MaterialSizeAmpacity at 75 °C
Copper2/0 AWG175 A
Aluminum4/0 AWG180 A

The rule does not apply to a subpanel feeder that carries only part of the house's load. A 200 A subpanel uses the full table above.

Ground wire for a 200 A circuit

NEC Table 250.122 sizes the equipment ground from the breaker: 6 AWG copper or 4 AWG aluminum for 200 A. Cable assemblies (NM-B, SER, UF) include a ground already sized for their gauge. A 200 A circuit carries up to 48,000 W at 240 V, or 38,400 W for a continuous load.

Common 200 A circuits

  • 200 A service, the standard for new single-family homes and electrified homes with heat pumps and EV charging.
  • 200 A feeder to a second panel or a detached building.

Feeding a subpanel? It needs four wires (two hots, a neutral and a ground), with the neutral and ground kept separate in the subpanel, and a detached building needs its own grounding electrode (NEC 250.32).

Size wire for your run

Safety. Installing a 200 A circuit or feeder needs a permit almost everywhere in the US. Equipment nameplates (minimum circuit ampacity and maximum overcurrent protection) override any general table, and local amendments to the NEC can be stricter.

Keep reading